| Input Channels |
8 single-ended analog inputs (common return) |
| Input Types |
- Voltage: 0_10 V DC, ±10 V DC - Current: 4_20 mA, 0_20 mA (jumper/software selectable per channel) |
| Resolution |
15-bit (1.22 µA or 1.22 mV per LSB) _ upgraded from 12-bit in ALG260 series
|
| Accuracy |
±0.15% of full scale at 25°C; ±0.3% over full temperature range |
| Update Rate |
8 ms for all 8 channels (125 Hz sampling) |
| Input Impedance |
>500 kΩ (voltage mode), 250 Ω ±0.05% (current mode) |
| Loop Power |
External 24 V DC required; HART 7 compatible
|
| HART Pass-Through |
Yes _ transparent HART 7 digital overlay (device ID, PV/SV, diagnostics) |
| Open Wire Detection |
Yes _ < 2 mA (current); <5% FSR (voltage); configurable alarm |
| Overrange/Underrange |
±10% beyond nominal; clamped with alarm
|
| Isolation |
1500 V RMS field-to-backplane; no channel-to-channel isolation
|
| Common Mode Rejection |
>95 dB @ 50/60 Hz |
| Noise Rejection |
Configurable digital low-pass (8_1024 Hz); adaptive 50/60 Hz notch filter
|
| Scaling & Linearization |
User-defined engineering units, square root (flow), 32-point custom table
|
| Diagnostics |
Open circuit, over/underrange, HART device status, loop impedance, module fault, backplane power monitoring
|
| Power Supply |
+5 V DC @ 160 mA (from backplane) |
| Power Consumption |
0.8 W maximum |
| LED Indicators |
Module OK (green), Fault (red), 8x Channel Active (green), HART Active (yellow, blinking)
|
| Configuration |
Proficy Machine Edition (PME) 9.0+; firmware-based field calibration, HART device manager integration
|
| Firmware |
Field-upgradable via PME or front micro-USB port |
| Operating Temperature Range |
0°C to +60°C |
| Storage Temperature Range |
-40°C to +85°C |
| Humidity |
5% to 95% non-condensing |
| Vibration |
IEC 60068-2-6 (5g, 10_150 Hz) |
| Shock |
IEC 60068-2-27 (30g, 11 ms) |
| Mounting |
Snaps onto VersaMax carrier base (IC200ACCxxx) |
| Dimensions |
4.33" x 2.60" x 1.77" (110 mm x 66 mm x 45 mm) |
| Weight |
0.46 lb (0.21 kg) |
| Enclosure Rating |
IP20 |
| Key Enhancements vs ALG260 |
15-bit resolution, 8 ms update, HART 7 pass-through, micro-USB port, enhanced filtering, improved EMC immunity |
| Standards Compliance |
IEC 61131-2, CE, UL, CSA, Class I Division 2, ATEX Zone 2, HART 7 Registered, RoHS 2, IEC 61000-6-2/4 (EMC)
|