| Input Voltage Range |
85–265 V AC |
| Nominal Input Voltage |
120/240 V AC |
| Input Frequency |
47–63 Hz |
| Input Power |
115 W maximum |
| Maximum Output Power |
75 W @ 0–60°C (32–140°F) |
| Inrush Current |
20 A maximum |
| Current Capacity |
1.5 A @ 1.2 V DC, 4 A @ 3.3 V DC, 13 A @ 5.1 V DC, 2.8 A @ 24 V DC |
| Hold-Up Time |
2 cycles @ 60 Hz, 2 cycles @ 50 Hz |
| Isolation Voltage |
250 V (continuous), Reinforced Insulation Type, tested @ 3250 V DC for 60 s |
| Power Dissipation |
Not specified |
| Terminal Connections |
External connection with redundant power supply cables (e.g., 1756-CPR2) |
| Wire Size |
2.5 mm² (14 AWG) solid or stranded copper wire, rated at 90°C or greater, max insulation 1.2 mm |
| Operating Temperature |
0°C to 60°C (32°F to 140°F) |
| Storage Temperature |
-40°C to 85°C (-40°F to 185°F) |
| Humidity |
5% to 95% (non-condensing) |
| Vibration Tolerance |
Not specified |
| Shock Tolerance |
Not specified |
| Dimensions |
17.5 x 14.5 x 13.7 cm (6.9 x 5.7 x 5.4 in) |
| Weight |
1.45 kg (3.2 lb) |
| Standards Compliance |
CE, UL, CSA (Class I, Div 2, Groups A, B, C, D), FM |