| Input Channels |
6 individually isolated thermocouple inputs, 2 cold-junction compensation (CJC) sensors |
| Input Types |
Thermocouple, millivolt |
| Supported Thermocouple Types |
B, C, D, E, J, K, L, N, R, S, T |
| Input Range |
-12 to 78 mV (1.4 µV/bit), -12 to 30 mV (0.7 µV/bit, high-resolution range) |
| Resolution |
16 bits |
| Data Format |
Integer (left justified, 2’s complement) or IEEE 32-bit floating point |
| Conversion Method |
Sigma-Delta |
| Module Scan Time |
25 ms minimum (floating-point, millivolt), 50 ms minimum (floating-point, temperature), 10 ms minimum (integer, millivolt) |
| Common Mode Rejection |
>80 dB at 60 Hz |
| Normal Mode Rejection |
>60 dB at 60 Hz |
| Accuracy |
Varies by thermocouple type, typically ±0.6°C (Type K) at 25°C |
| Calibration |
Factory calibrated, user calibration supported |
| Power Dissipation |
4.6 W maximum |
| Backplane Current Load |
200 mA @ 5.1 V DC, 120 mA @ 24 V DC, 2 mA @ 24 V DC (auxiliary) |
| Isolation |
250 V (continuous), reinforced insulation type, inputs to backplane and channel-to-channel |
| Cold Junction Compensation |
2 CJC sensors, accuracy ±0.3°C |
| Terminal Connections |
20-pin removable terminal block (RTB), 175 |