| Output Channels |
2 single-ended analog outputs |
| Output Types |
- Voltage: ±10 V DC - Current: 0_20 mA (default), 4_20 mA (configurable) |
| Resolution |
12-bit (1 LSB = 5 mV or 10 µA) |
| Accuracy |
±0.5% of full scale at 25°C; ±1.0% over temperature range |
| Update Rate |
_ 1 ms per channel |
| Load Capability |
- Voltage: _ 1 kΩ - Current: _ 500 Ω |
| Settling Time |
< 300 µs (to 0.1% of final value) |
| Output Protection |
Short-circuit (current mode), open-circuit detection |
| Isolation |
500 V AC channel-to-backplane; no channel-to-channel isolation
|
| Common Mode Voltage |
±12 V max |
| Diagnostics |
Short-circuit, open load, module fault, LED status
|
| Scaling |
User-defined engineering units via STEP 7-Micro/WIN SMART
|
| Power Supply |
+24 V DC (20.4_28.8 V) via L+/M terminals
|
| Power Consumption |
80 mA @ 24 V DC |
| Backplane Current |
20 mA @ 5 V DC |
| LED Indicators |
- SF (red): System fault - 24V (green): Field power OK |
| Configuration |
STEP 7-Micro/WIN SMART v2.4+; per-channel range, alarms, fallback |
| Address Space |
4 bytes output (2 channels _ 16-bit) |
| Operating Temperature Range |
-20°C to +60°C (horizontal), -20°C to +50°C (vertical) |
| Storage Temperature Range |
-40°C to +70°C |
| Humidity |
5% to 95% non-condensing |
| Vibration |
IEC 60068-2-6 (5g, 10_150 Hz) |
| Shock |
IEC 60068-2-27 (15g, 11 ms) |
| Mounting |
Snaps onto S7-200 SMART expansion bus (right side) |
| Dimensions (W x H x D) |
70 mm _ 80 mm _ 62 mm |
| Weight |
0.18 kg |
| Enclosure Rating |
IP20 |
| Standards Compliance |
IEC 61131-2, CE, UL, cUL, FM Class I Div 2, RoHS, China RoHS
|