| Number of Channels |
4 (fully isolated) |
| Output Type |
Voltage (0_10 V DC or ±10 V DC, software selectable per channel) |
| Output Range |
0_10.5 V or _10.5 V to +10.5 V (±5% over-range) |
| Resolution |
12-bit (4,096 counts over 0_10 V; 8,192 counts over ±10 V) |
| Accuracy |
±0.1% of full scale at 25°C |
| Update Rate |
_ 0.3 ms per channel (1.2 ms full scan) |
| Load Capability |
_ 2 kΩ (min load resistance); 5 mA max per channel
|
| Open-Loop Detection |
> 10.5 V or < _10.5 V triggers fault (configurable) |
| Isolation |
250 V RMS continuous channel-to-channel and channel-to-backplane |
| Power Supply |
Backplane: 5 V DC @ 240 mA max No external loop power required
|
| Operating Temperature |
_40°C to +60°C (extended industrial range) |
| Storage Temperature |
_40°C to +85°C |
| Protection Rating |
IP20 |
| Dimensions |
90 mm (H) _ 50 mm (W) _ 75 mm (D) (standard VersaMax module) |
| Weight |
0.21 kg (0.46 lbs) |
| Connectors |
Removable screw terminal block (8 terminals: 4 outputs + 4 returns) |
| LED Indicators |
Module OK (green), Fault (red), 4x Channel Active (green)
|
| Diagnostics |
Open loop, over-range, under-range, module fault (via %Q/%AQ status bits) |
| Certifications |
CE, UL, cUL, CSA, Class I Div 2, ATEX Zone 2
|
| Standards Compliance |
IEC 61131-2, EN 61000-6-2/4 (EMC), UL 508, CSA C22.2
|