Product Description
Product Overview
| Parameter | Details |
|---|---|
| Part Number | IC200BEM002 |
| Product Name | VersaMax PROFIBUS-DP Network Slave Module |
| Application | Industrial automation and process control systems for distributed I/O networking |
| Compatibility | GE VersaMax PLC system; integrates with VersaMax CPUs, power supplies, and communication modules via backplane |
| Function | Exchanges PLC reference table data over PROFIBUS-DP network as conventional bit- and word-type I/O data |
Functional Specifications
| Parameter | Details |
|---|---|
| Network Type | PROFIBUS-DP Slave |
| Stations Supported | 32 without repeaters; up to 125 with repeaters |
| Data Exchange | Up to 384 bytes I/O data (244 bytes input or output) |
| Baud Rate | 9.6 kBaud to 12 MBaud (auto-detected) |
| Connector Type | 9-pin D-sub |
| LED Indicators | Power OK, Network Status, Module Fault |
| Power Consumption | 5 V DC, 150 mA (backplane-powered) |
| Operating Temperature | 0°C to 60°C |
| Storage Temperature | -40°C to +85°C |
| Protection Rating | IP20 |
| Dimensions | Standard VersaMax module size (approximate: 90 mm x 50 mm x 75 mm) |
| Weight | Approximately 0.2 kg |
| Certifications | CE marked; UL, cUL, CSA compliant |
| Standards Compliance | IEC 61158 compliant for PROFIBUS; IEC 61131-2 for programmable controllers |
Ordering Information
| Parameter | Details |
|---|---|
| Part Number Configuration | IC200BEM002 (PROFIBUS-DP Slave Module for VersaMax) |
| Available Options | Variants for master modules (e.g., IC200BEM003); refurbished options |
| Customization | Fieldbus integration or extended temperature range available upon request |