| Input Voltage |
85–132 V AC / 170–264 V AC (auto-select via jumper) |
| Input Frequency |
47–63 Hz |
| Input Current |
2.4 A @ 120 V, 1.3 A @ 230 V |
| Inrush Current |
≤ 45 A @ 264 V (cold start) |
| Power Factor |
≥ 0.95 (active PFC) |
| Output Voltage |
24 V DC ±3% (23.28–24.72 V), adjustable via potentiometer (±5%) |
| Output Current |
0–10 A (continuous), 12 A peak (< 1 min) |
| Output Power |
240 W |
| Ripple/Noise |
≤ 100 mVpp (20 MHz bandwidth) |
| Efficiency |
≥ 88% @ full load |
| Hold-Up Time |
≥ 20 ms @ 120 V, ≥ 150 ms @ 230 V |
| Overload Protection |
Electronic current limit @ 10.5–12.5 A, auto-recovery
|
| Short-Circuit Protection |
Yes — constant current, hiccup mode
|
| Parallel Operation |
Yes — up to 3 units (with 6ES7307-1KA02-0AA0 load-sharing module) |
| Redundancy |
Yes — with 6ES7307-1KA02-0AA0 or SITOP RED1200/RED2400
|
| Remote ON/OFF |
Yes — via 24 V DC signal (terminal R) |
| Isolation |
3000 V AC input-to-output, 1500 V AC input-to-ground |
| EMC |
EN 61000-6-2 (immunity), EN 61000-6-4 (emission), Class B
|
| Diagnostic LED |
Green: Output OK Red flashing: Overload/short-circuit Yellow: Remote OFF |
| Output Terminal |
L+ / M (screw terminals, 0.5–10 mm²) |
| Input Terminal |
L / N / PE (screw terminals, 0.5–4 mm²) |
| Remote Control |
R (24 V DC input) — 0 V = ON, 24 V = OFF |
| Power Supply to Backplane |
Direct via S7-300 backplane bus
|
| Power Loss |
30 W @ full load |
| Operating Temperature Range |
0°C to +60°C (derating >50°C: 3%/K) |
| Storage Temperature Range |
-40°C to +85°C |
| Humidity |
5% to 95% non-condensing |
| Vibration |
IEC 60068-2-6 (2g, 10–150 Hz) |
| Shock |
IEC 60068-2-27 (15g, 11 ms) |
| Mounting |
35 mm DIN rail or S7-300 rack (leftmost slot) |
| Dimensions (W x H x D) |
100 mm × 125 mm × 120 mm |
| Weight |
1.1 kg |
| Enclosure Rating |
IP20 |
| Certifications |
CE, UL, cUL, FM Class I Div 2, ATEX Zone 2, China RoHS, EAC, KC, SEM F47
|