| Input Channels |
7 independent thermocouple/mV inputs |
| Input Types |
Thermocouple: J, K, T, S, R; Millivolt: ±100 mV (selectable per channel) |
| Resolution |
16-bit |
| Accuracy |
±0.5°C typical (thermocouple), ±0.05% FSR (mV) |
| Update Rate |
60 ms @ 60 Hz, 70 ms @ 50 Hz |
| Input Impedance |
>10 MΩ |
| Cold Junction Compensation |
Local or remote (software selectable); ±1°C accuracy |
| Isolation |
250 V AC continuous, 1500 V AC (1 min) field-to-logic |
| Open Wire Detection |
Yes, with upscale/downscale alarms |
| Diagnostics |
Overrange/underrange, open circuit, CJC fault, module fault |
| Power Supply |
+5 V DC @ 125 mA (backplane) |
| Power Consumption |
0.625 W maximum |
| Operating Temperature Range |
0°C to +60°C |
| Dimensions |
4.3" x 2.63" x 1.95" (109 mm x 67 mm x 50 mm) approximate |
| Weight |
0.2 kg |
| Standards Compliance |
IEC 61131-2, CE, UL, CSA |