| Input Channels |
15 differential current inputs |
| Input Range |
4_20 mA (default); 0_20 mA (configurable via software) |
| Resolution |
12-bit (5 µA per step) |
| Accuracy |
±0.25% of full scale at 25°C; ±0.5% over full temperature range |
| Update Rate |
30 ms for all 15 channels (2 ms per channel sequential scan) _ improved from 40 ms in Rev D
|
| Input Impedance |
250 Ω (precision shunt resistor, 0.05% tolerance) |
| Loop Power |
External 24 V DC loop supply required; HART 7 fully compliant
|
| HART Pass-Through |
Yes _ bidirectional HART 7 (multivariable, device config, diagnostics, burst mode) |
| Open Wire Detection |
Yes _ reports < 1.8 mA as fault; upscale/downscale configurable per channel
|
| Overrange/Underrange |
Clamps at 0 mA and 24 mA; configurable alarm thresholds
|
| Isolation |
250 V RMS channel-to-channel; 1500 V RMS field-to-backplane
|
| Common Mode Rejection |
> 90 dB @ 50/60 Hz |
| Noise Rejection |
Configurable digital low-pass (8_512 Hz); adaptive 50/60 Hz notch filter
|
| Scaling & Linearization |
User-defined engineering units, square root (flow), 16-point custom table per channel
|
| Diagnostics |
Open circuit, over/underrange, HART device health, loop resistance monitoring, module fault, backplane power loss, self-test
|
| Power Supply |
+5 V DC @ 190 mA (from backplane) |
| Power Consumption |
0.95 W maximum |
| LED Indicators |
Module OK (green), Fault (red), 15x Channel Active (green), HART Comm (yellow, blinking)
|
| Configuration |
Proficy Machine Edition (PME) 9.0+; web-based configuration, HART device manager, firmware upgrade via USB
|
| Firmware |
Field-upgradable via front micro-USB port or PME |
| Operating Temperature Range |
0°C to +60°C |
| Storage Temperature Range |
-40°C to +85°C |
| Humidity |
5% to 95% non-condensing |
| Vibration |
IEC 60068-2-6 (5g, 10_150 Hz) |
| Shock |
IEC 60068-2-27 (30g, 11 ms) |
| Mounting |
Snaps onto VersaMax carrier base (IC200ACCxxx) |
| Dimensions |
4.33" x 2.60" x 1.77" (110 mm x 66 mm x 45 mm) |
| Weight |
0.50 lb (0.23 kg) |
| Enclosure Rating |
IP20 |
| Revision C Enhancements |
30 ms update (25% faster), full HART 7, micro-USB port, loop resistance diagnostics, web config, improved EMC immunity |
| Standards Compliance |
IEC 61131-2, CE, UL, CSA, Class I Division 2, ATEX Zone 2, HART 7 Registered, RoHS 2, IEC 61000-6-2/4 (EMC)
|