| Input Channels |
8 analog inputs (single-ended, isolated) |
| Input Types |
- Voltage: ±10 V, ±5 V, ±2.5 V, 0_10 V - Current: 0_20 mA, 4_20 mA |
| Resolution |
- 13-bit (unipolar, 2.44 µA or 1.22 mV) - 16-bit with sign (bipolar, 0.305 µA or 0.153 mV) |
| Accuracy |
±0.1% of full scale at 25°C; ±0.2% over temperature range |
| Conversion Time |
2 ms per channel (16 ms for all 8 channels) |
| Input Impedance |
- Voltage: _ 1 MΩ - Current: 250 Ω (precision resistor) |
| Common Mode Voltage |
±35 V max |
| Isolation |
500 V AC channel-to-backplane; no channel-to-channel isolation
|
| Open Wire Detection |
Yes _ in 4_20 mA mode (< 1.5 mA); configurable alarms
|
| Overrange/Underrange |
±10% of nominal range; clamped with alarm
|
| Diagnostics |
Wire break (current), overflow/underflow, module fault, LED status
|
| Scaling |
User-defined engineering units, linear scaling, alarm thresholds
|
| Address Space |
16 bytes (8 channels _ 16-bit) |
| Power Supply |
From S7-1200 backplane (5 V DC) |
| Backplane Current |
80 mA @ 5 V DC |
| Power Loss |
1.5 W typical |
| LED Indicators |
- SF (red): System fault - DIAG (green): Module OK |
| Configuration |
TIA Portal V18+; per-channel range, resolution, filter, alarms |
| Connection |
Front removable 20-pin screw terminal (push-in option via 6ES7292-1BL30-0XA0) |
| Wire Size |
0.2_1.5 mm² (24_16 AWG) |
| Operating Temperature Range |
-20°C to +60°C (horizontal), -20°C to +50°C (vertical) |
| Storage Temperature Range |
-40°C to +70°C |
| Humidity |
5% to 95% non-condensing |
| Vibration |
IEC 60068-2-6 (5g, 10_150 Hz) |
| Shock |
IEC 60068-2-27 (15g, 11 ms) |
| Mounting |
Snaps onto S7-1200 expansion bus (right side) |
| Dimensions (W x H x D) |
45 mm _ 100 mm _ 75 mm |
| Weight |
0.18 kg |
| Enclosure Rating |
IP20 |
| Certifications |
CE, UL, cUL, FM Class I Div 2, ATEX Zone 2, China RoHS, KC, RCM, EAC
|